hola

En Español
 
 
  Systems
     
Constant Volumen
 
  Hydraulics
 
  Energy Efficiency
 
  Equipment
 
   

Page Views
9556
Back to www.nanomagnetics.org
 
    Contact US
    Advertise with Us
    Related Links

Primary-Secondary Schemes
Variable volume/variable speed

The variable volume/variable speed (VV/VS) scheme is a variation of the constant volume/constant speed (CV/CS) design with a grater energy efficient performance (Fig. 11). Basically, the VV/VS scheme differs from the CV/CS as to the way the system tracks thermal load. In CV/CS systems the volume of chilled water circulating is the same at all times and thermal load variation is reflected in system delta T fluctuation.
On the other hand, in VV/VS systems the flow will track the load allowing considerable energy saving in pumping at part load.

Click to get the image full size
Fig. Nº11 VV/VS primary-secondary pumping system.
Click on image to enlarge
To achieves such goal the three way valves that always bring an alternative "path" to the flow at part load condition, must be replaced by two way valves. The secondary pumps will now be driven by VSD that allows variable speed operation according to flow terminals demand.


The control loop closes with a differential pressure sensor that must be appropriately situated in the hydraulic circuit. Such device will send a sign proportional to the increase of the pressure in the zone of the circuit that is being monitored. A differential pressure setpoint will then be fixed in order to allow enough flow in the monitored zone at all load conditions. At part load, when two way valves modulate to close, the differential pressure setpoint will then be maintained by a proportional reduction of the pump speed that means system flow reduction. The pumping power consumption is a cubic function of flow change so a 50 %
speed reduction leads to an 87.5 % of energy saving.
Operating a VV/VS primary-secondary pumping system can lead to three flow conditions that are:


Secondary circuit flow equals primary circuit flow.
Secondary circuit flow grater than primary circuit flow.
Primary circuit flow grater than secondary circuit flow.

Secondary circuit flow equals primary circuit flow: This is an uncommon flow condition because it means the system is completely balance which is rarely to find in real life systems (Fig. 12). However, it is worth analyzing such a flow condition in order to achieve a better knowledge of the system operation. The constant volume that circulates through the secondary circuit is equal to 1000 GPM, the chilled water supply (CWS) temperature is 45 F with a temperature rise of 10 F. The primary circuit is equipped with three equal chillers of 415 Ton each one. The flow that circulates through the active chiller equals 415 Ton x 24 x 1/10 F = 1000 GPM. So, when only one chiller is on, primary flow equals secondary flow, and no water circulates through the common pipe. At this moment the thermal load is 415 Ton.


The remainder of the time of the secondary or load flow will be greater or less than the primary flow. The moment the load increases in the space, the two-way valves begin modulating to a more open position and deliver additional chilled water to satisfy the additional load. When this occurs, the pressure and flow relationship changes such that the distribution flow is greater than the production flow (Fig. 13).
Click to get the image full size
Fig. Nº12 Secondary flow equals primary flow.
Click on image to enlarge

Secondary circuit flow grater than primary circuit flow:
In this case the thermal load has increased from 415 Ton to 500 Ton. The flow through the active chiller remains the same (1000 GPM) but the secondary flow has risen to 1200 GPM due to a more open position of the two way valves. Such a secondary flow increase is a reaction of the VSD that steers the pump aimed to keeping the differential pressure setpoint. To balance the mass flow, the excess 200 GPM must run through the common pipe. The temperature of the 200 GPM in the common pipe is 55 F. This blends with the 1000 GPM of 45 F supply water, resulting in 1200 GPM of 46.7 F blended supply water
Click to get the image full size
Fig. Nº13. Secondary flow grater than primary flow.
Click on image to enlarge
A higher supply water temperature profoundly reduces cooling coil capacity, especially latent cooling capacity. One solution could be considering higher supply water temperatures during the coil selection process at the beginnings of the projects. Other options as chiller temperature reset can be considered. Within the limits of the type of machine, chiller temperatures can be reset to a lower temperature to compensate for the increased load and secondary flows. In essence, more capacity is provided at a lower operating efficiency.
The increase in cost of chiller operation due to the lowering of the chiller supply temperature can range from 1 to 3 percent per degree of reset. This is a very desirable alternative, especially when large chillers are in use. The longer the start of a lag chiller can be delayed, the better it will perform when it is finally brought on line. If a small portion of the load requires a fixed temperature, a small chiller in series with the load may also be considered.

Primary circuit flow grater than secondary circuit flow:
When thermal load keeps rising up to 625 Ton and another chiller is brought on line the third flow condition appears (Fig. 14). The primary circuit flow is 2000 GPM and through the secondary circuit circulates 1500 GPM. The 500 GPM excess must flow through the common pipe at the chilled water supply temperature of 45 F and blends with the 1500 GPM secondary chilled water return to produce 2000 GPM at a reduced entering chilled water temperature of 52.5 F. All chilled water returning from the loads is blended prior to reaching the chillers. All of the chillers on line will therefore be receiving the same temperature water at their return.
Click to get the image full size
Fig. Nº14. Primary flow grater than secondary flow.
Click on image to enlarge
When the system is piped in this manner, the chillers will always be equally loaded. Furthermore, the chillers will always be subjected to their design flow at an equal temperature. Because the chillers are receiving their design flow rate at 52.5 F rather than the design temperature of 55 F, the chillers will be “unloaded” at the ratio of: (1- (55 F –52.5 F)/(55 F – 45 F))*100 = 75 %
The origin of the three flow conditions analyzed lies in the different between the linear nature of the thermal load and the stepped way the chiller plant acts to track it. As the two-way valves modulate in response to a varying load, the flow follows directly. The more chillers in the plant, the smaller the steps to track the load. The addition of chillers in a variety of sizes makes the incremental steps smaller. The additional chillers and variety of chiller sizes can produce a curve that is nearly linear. When the chiller plant is designed to produce a near-linear flow function, the flow in both directions through the common pipe and the consequences of blending supply with return chilled water are minimized. Increasing of supply water temperature then lasts for a shorter duration which is a very critical factor in design regions where humidity control is a concern.


 

Home | | Link To Us | | Privacy Policy | Contact Us

< Copyright www. nanomagnetics.org 2007>