In chilled water plants, centrifugal pumps
provide the required differential pressure
to circulate water through the chilled and
condenser water distribution system.
In the centrifugal pump, an electric motor
rotates an impeller that adds energy to the
water after it is directed into the center
of the rotating impeller.
The combination of centrifugal and rotational
force imparts velocity to the water.
The pump casing is then designed to maximize
the conversion of velocity energy of the fluid
into pressure energy (Fig.
90).
Fig.
Nº90.
Pump
casing schematic section.
Click on
image to enlarge
Pump Types:
The most of the pumps used in the HVAC industry
are single stage (one impeller) volute-type pumps
that have either a single inlet or a double inlet
(double suction). Double suction pumps are used
in high volume applications; however either a
single inlet or double inlet pump is available
with similar performance characteristics and efficiencies.
Close-Coupled, Single Stage,
End-Suction Pump: The closed-coupled pump
has the impeller mounted on a motor shaft extension.
The pump is mounted on a horizontal motor supported
by the motor foot mountings.
Fig. Nº91.
Closed-Coupled End-Suction Pump
Click on image
to enlarge
A solid concrete pad is required
for mounting. This compact pump has a single horizontal
inlet and vertical discharge (Fig.
91). The motor and pump can
not be misaligned and they take up less floor space than
flexible-coupled pumps. However, to replace the special
motor with an extended shaft that is used can be difficult
to get after a breakdown. Frame-Mounted, End-Suction Pump
on Base Plate: The motor and
pump are mounted on a common rigid base plate for horizontal
mounting. Mounting requires a solid concrete pad. The motor
is flexible-coupled to the pump shaft. For horizontal mounting,
the piping is horizontal on the suction side and vertical
on the discharge side (Fig.
92). The flexible-coupled
shape allows the motor or pump to be removed without disturbing
the other. However, the flexible coupling requires very
careful alignment and a special guard. The flexible-coupled
pump is usually less expensive than the close-coupled pump.
Double-Suction pumps:
The water is introduced on each side of the impeller and
the pump is flexibly connected to the motor. Typically,
motor and pump are mounted on a common rigid base plate
for horizontal mounting (Fig.
93). Double-suction pumps
are preferred in application over 1000 GPM because its very
high efficiency and can be opened, inspected and serviced
without disturbing the motor, impeller or the piping connections.
The pump case can be split axially (parallel to the shaft)
or vertically for servicing. This pump takes more floor
space than end suction pumps and is more expensive.
Vertical In-Line Pumps: It
is also a closed-coupled pump that has the motor mounted
on the pump casing (Fig 94).
These pumps have the suction and discharge connections arranged
so they can be inserted directly into a pipe. Mounting requires
adequately spaced pipe hangers and, sometimes, a vertical
casing support. In the past, in-line pumps were used almost
exclusively for small loads with low heads but now the widest
rage of sizes is available. Considerable space saving can
be achieved using in-line pumps but extra care must be taken
to assure that pipe stress are not transferred to the pump
casing.
Fig. Nº92.
Frame Mounted End-Suction
Pump on Base Plate .
Click on image
to enlarge
Fig. Nº93. Double-Suction
Pumps
Click on image
to enlarge
Fig. Nº94. Vertical
In-Line Pumps
Click on image
to enlarge
Pump Performance Curves
The performance curve
is the easiest and most satisfactory way
to show graphically the relationship between
head, capacity, horsepower, etc., of any
pump (Fig. 95).
For a given rotational speed and impeller
size, the performance of a pump can be represented
on a head-capacity curve of total developed
head in feet of water versus flow in gallons
per minute.
Fig.
Nº95.
Pump Curve for Different Impeller Sizes
Click on
image to enlarge
Total dynamic head (TDH) is the difference between
suction and discharge pressure and includes the difference
between the velocity head at the suction and discharge
connection. The lines sloping downward from left to
right represent the varying quantities of water delivered
by the pump with variations in head or pressure for
a given impeller size.
The intersection of this line with zero delivery line
shows the “shut-off head”, which is the
pressure developed by the pump when the discharge
valve is shut.
Starting from the shut-off head, as the pump delivers
more water, the mechanical efficiency of the pump
increases until a “best efficiency point”
(BEP) is reached. Increasing the flow further decreases
the efficiency until a point known as “end of
curve” where the manufacturer no longer publishes
the performance. As the impeller gets smaller, the
pump efficiency also decreases.
The power requirements are also shown on the performance
curve. The horsepower line that does not cross the
pump curve is called “non-overloading”
horsepower because operation at any point on the published
pump curve will not overload the motor.
Parallel Operation
The primary purpose of operating pumps in parallel
is to allow a wider range of flow than would be
possible with a single fixed speed pump for systems
with widely flow demand.
Usually there are no more than three or four pumps
operating in parallel.
The combined parallel pump curve can be drawn
holding the head constant and adding the flow.
Fig. 96 shows a combined pump curve of
a system with three identical pumps operating
in parallel.
Fig. Nº96.
Combined
Performance Curves for Three Identical Pumps
Operating in Parallel
Click on image
to enlarge
Curve A represents the head-flow
curve for any one of the pumps. Curve B is the combined
pump curve for two pumps operating at the same time in parallel
and curve C represents the combined performance for the
three pumps. Notice that at any head value, the flow on
curve B is twice the flow at the same head on curve A. Likewise,
flow on curve C is three times the flow on curve A for the
same head value. Curve X represents the system head curve.
Points a, b, and c represents the flow that is delivered
by the pumps at the three operating conditions which are:
a single pump, two pumps and all (three) pumps operating
at the same time.
Series Operation
In series operation, the discharge of one pump feeds
the suction of a second pump (Fig 97). Unlike parallel
operation, series pump curve can be drawn holding
the flow constant and adding the head. Series operation
allows that commercially available equipment can
be used in a particular system because sometimes
a single pump operation would result in a pump with
an extremely high head and thus an equally high
horsepower. For example, distributing pumping schemes
applied in chilled water plants avoid using to big
pumps for chilled water circulation that create
unnecessary overpressure at the buildings close
to the plant. Small pumps situated just at the building
they feed mitigate the overpressure problem and
at the same time save considerable pumping energy.
Such schemes are based on the series pumps operation
principles.
Fig. Nº97.
Combined Performance Curves for Three Identical
Pumps Operating in Series
Click on image
to enlarge
System Curves
The system curve defines the system head required to produce
a given flow rate for a liquid and its characteristics in
a piping system design. To produce a given flow, the system
head most overcome pipe friction, inside pipe surface roughness,
actual fitting losses, actual valve losses, resistance to
flow due to fluid viscosity, and possible system effect
losses. The general shape of this curve is parabolic since
the head loss is proportional to the square of the flow.
In closed systems like chilled water distribution loops,
the head varies only with flow variations, so when there
is no flow, the head value is also nil
(Fig 98).
However, in an open system like piping
circuit between a refrigerant plant condenser and its
cooling tower, the elevation difference between the water
level in the tower pan and the spray distribution pipe
creates a fixed (static) head loss. That fixed loss occurs
at all flow rates, so it is, therefore, and independent
head loss (Fig. 99).
Variable Speed Pumping
The reasons why variable speed pumping saves energy are
illustrated in Fig. 100.
The pump (curve A) must operate between the flows marked
as 1 and 2 in the figure. The higher flow rate is achieved
where the pump curve intersects the system (curve X) at
point ax. With a constant speed pump, the lower flow rate
is obtained by throttling the pump discharge to steepen
the system curve until the new system curve intersects
the pump curve at the lower required flow rate, at point
ay.
Fig. Nº98.
Typical Closed System
Head Curve .
Click on image
to enlarge
Fig. Nº99. Typical
Open System Head Curve
Click on image
to enlarge
Fig. Nº100. Capacity-Head
and Efficiency Curves for Two Flow Rates Using
Throttling and Variable Speed
Click on image
to enlarge
If instead of throttling, the pump
were slowed down it would produce a new head-flow and efficiency
curves, show n on Fig. 100 as light solid lines. The intersection
of this slower speed head-flow curve (curve B) with the
original system head curve X (point bx), represents the
flow rate delivered by the pump operating at reduced speed.
The difference in head between points ay and bx represents
the head wasted across the control valve when the constant
speed pump is throttled instead of slowed down.
The affinity laws are rules that govern the performance
of a pump under varying conditions of flow and pressure.
The laws can be roughly stated as follows: -
Flow varies with rotating speed -
Head varies with the square of the rotating speed -
Brake horsepower varies as the cube of the rotating speed
According to the last affinity law, if the slower flow rate
in the Fig. 100 (marked as 1) were half the higher flow
rate (marked as 2) then the power necessary to provide the
slower flow rate would be (0.5)3 = 0.125 or 12.5 % of the
power required for the higher flow rate. It means an energy
saving of 87.5 %. Such savings justify the applications
of variable speed pumping because of its low pay-back period.
Note also that, at lower flow rate using a constant speed
the efficiency lowers, as can be seen in the Fig. 100. On
the contrary, when using variable speed pumping the pump
efficiency curve shifts to the left at lower flow rate and
the pump runs at least as efficient as at higher flow.
In addition to the energy savings associated with using
variable speed pumping, there are other important benefits
related to the health of the pump. Operating at reduced
speed to obtain a lower flow rate produces lower radial
bearing loads, which should give longer bearing life and
less chance of bearing or seal failure. Besides, when the
pump operates closer to its BEP less internal circulation
of the fluid is produced. Thus, erosive damage to the pump
is also mitigated.
Variable speed pumping allows the continued tuning of the
system so that pump is performing optimally, despite of
changes in either the system or the pump. If head requirements
change over time, due to build-up of corrosion in pipe lines,
the pump can simply be speeded up to account for the higher
head required. Likewise, if the pump impeller wears and
clearances become wider, the speed can be adjusted up to
keep the pump from delivering less flow. The fudge factors
often used in pump head calculations which may result in
pumps over-sizing are essentially eliminated when variable
speed pumping is applied.
The variable frequency drive (VFD) is by far the most commonly
device to achieve variable speed pumping. A VFD work as
a controller for a standard A.C. motor, adjusting the frequency
and voltage to achieve a variable output speed. VFDs represent
the state of the art for speed variation; they can be adapted
to an existing standard motor allowing it to operate in
a wide speed range without excessive energy losses. It is
worth also pointing that VFDs are considerably more efficient
than the other methods of achieving variable speed used
in the past as fluid couplings and hydro-viscous (slip-clutch)
arrangements, among others.
However, VFDs have some disadvantages as possible negative
impact on power quality, motor noise, electromagnetic interference
(EMI), radio frequency interference (RFI), and nuisance
tripping. The efficient of the motor and drive combined
should be considered as well as the type of motor being
connected and the distance between the drive and the motor,
and numerous accessories. Therefore, in each variable speed
application several issues must be carefully followed to
ensure successful results.
In summary, variable speed pumping is a very desirable alternative
to reduce pumping costs for systems with a wide range of
pump flow requirement. It could be used in retrofitting
projects without buying new motors. Lower bearing loads
and overall better health of the pump is achieved while
fine-tune speed in response to change in the system or pump.