hola

En Español
 
 
  Systems
 
  Hydraulics
 
  Energy Efficiency
     
Cooling Warter
 
  Equipment
 
   

Page Views
554
Back to www.nanomagnetics.org
 
    Contact US
    Advertise with Us
    Related Links

Distributing Water, Energy Efficiency

In chilled water systems, pumping normally draws from around 6 to 12 % of the total annual plant energy consumption. Older chilled water plants designs circulate constant volume of chilled water through chillers (primary loop) and building (secondary loop), no matter if the cooling load is large or small. If loads are small, the constant volume of chilled water is diverted around the cooling coils by three-way valves. As thermal loads are essentially variable, variable flow systems, where flow tracks the thermal load, have emerged as the most efficient pumping strategy that allows considerable reduction of the total energy consumption of the plant.
Selecting Pumps
Always select a pump at, or close to, its "best efficiency point" (BEP). The "preferred operating region", headed by the BEP, is established on pump-specific speed basis. Specific speed (Ns) is a dimensionless index used to describe the geometry of pump impellers and to classify them as to their type. Such index allows explaining, among other things, the wide variation in the value of efficiency at the BEP for different pumps.
The BEP represents a combination of head and flow produced by the pump where the efficiency is at its highest. All other things being equal, high efficiency also represents the minimum horsepower for that head-and-flow combination. Because it is rare that an application duty point will just happen to land on the BEP, there are guidelines to help you make the best choice.
Because head calculations are more uncertain than flow calculations, and because designers are likely to add safety factors, it makes sense to pick a constant-speed pump with the required duty point to the left of the BEP. By doing that, the pump will move toward higher efficiency as it reacts to lower-system head loss.
By selecting pumps that operate in the center or high efficiency part of the curve most of the time, we can lower operating costs and lengthen the life of pump seals and bearings. This is because the pump impeller generates increasingly high radial loads as its point of operation moves away from BEP toward lower efficiency points.
The pump net positive suction head (NPSH) is a term that has extremely limited usage for closed systems as chilled water circulation loops. Most closed air-conditioning system pump application does not require NPSH evaluation because it is possible to obtain adequate pump suction pressurization.
Larger pumps can be equipped with a range of impeller diameters. It is not good practice to choose a pump with either the largest or the smallest impeller. In doing this you will limit your ability to fine-tune the pump's performance after it is installed. Once installed you can measure the pressure difference across the pump and convert it to head being produced by the pump (and demanded by the system). If an impeller is larger than required for the system, it can be "trimmed" by putting it on a lathe, reducing the diameter, and rechecking the balance.
Trimming an impeller is easy and inexpensive. It is an excellent way to counteract the oversizing that might have resulted because of errors in early calculations. If a pump was selected with the smallest diameter impeller and it is still too large, it can not be trimmed. A similar situation exists if the largest diameter impeller has been selected. If the pump is undersized, there is no way to install a larger impeller and increase capacity. This situation is seldom encountered, but it could happen. And the solution is probably pretty expensive.
The horsepower savings between the different operating points can be determined by looking at the pump curve, and if you know kilowatt-hour costs you can figure your savings. Once you get the cost savings per year for trimming the impeller, a simple payback period can be determined to see if trimming is economically feasible. Payback periods of less than a year are not uncommon.
Distribution Pumps Arrangements

The distribution loop (secondary loop) of a chilled water plant uses any of several possible primary-secondary pumping situations or smaller pumps in series or parallel arrangement. These applications offer a great deal of flexibility, redundancy, and possibly cost savings if the flow requirement varies with time.

The distribution loop in Fig. 60 has three circuits. The circuit 1 has two identical pumps, one operating and the other in standby. Such arrangement ensures a 100 % back-up pumping capability in case of active pump failure. On the other hand, circuit 2 and circuit 3 have a standby pump that is common to both circuits.
Click to get the image full size
Fig. Nº60. Two secondary pumps arrangement. Circuit 1 has one pump operating and one standby. Circuit 2 and circuit 3 sharing a common standby pump.
Click on image to enlarge
It means both circuits have a back-up pumping capability of 50 % respect the total flow handled by both. It is obvious that sharing pumps allows lower initial pumping investment, which could be demanded by a limited budget, but the maintenance staff or contractor must be able to face the damage as soon as possible or chilled water feeding to both circuits will collapse if the standby pump brought on line trips. Chilled water plant designers must then face the trade-off between initial pumping costs and back-up pumping requirements in each particular project.

Sometimes a secondary pumping scheme is not the most efficient pumping distribution strategy. For example: In a big system as a campus, the pressure needed to pump the entire hydronic net is large and it is advantageous to place a third set of pumps out in the system to avoid imposing high pressure on the equipment close to the pumps' discharge.
In certain secondary pumping scheme the same head may be imparted to all chilled water passing through the distribution pumps, whether it is making the short trip through the closest building or the longest trip through the hydraulically most distant building. The extra head imparted to chilled water passing through the closer buildings must be wasted across balancing valves and/or throttling valves at those buildings.
Only the small fraction of the total chilled water flow going to the most distant building is produced without wasted energy.

A better strategy to pump distant loads is via distributed pumping. Distributed building pumps assume the function of secondary pumps, so each pump is sized to deliver its building's flow at just the head needed to pump the building hydronic loads and draw the chilled water through the mains from the center plant.

The practices used in selecting pumps for series or parallel operation are roughly similar to those discussed above, but there are some important differences. The motors provided for parallel pumps must be chosen for the single-pump operating mode because the single pump will run out on its curve and draw more horsepower than when both pumps are operating together. Motors for pumps in series must be selected to handle the horsepower requirements when both pumps are running.


Parallel constant speed (C/S) pumps have been used for many years in a simple method for achieving pump power reduction for variable volume (two-way valve controlled) HVAC systems. Paralleled C/S pumps compete favorably with variable speed (V/S) pumps, particularly in smaller systems where variable system piping head loss is a small proportion of total system head needs.
Parallel C/S pumps are usually selected so that each pump provides half design flow, which means that each pump provides half of design HP needs. The parallel C/S pump power correlation with a single C/S pump, assuming similar pump efficiencies, is shown in Figure 61.
A similar advantage for parallel C/S pumps in comparison with V/S pumps occurs when the variable head loss in a V/S pumped system is a low percentage of total pump head. This is shown in Figure 62.

Click to get the image full size
Fig. Nº61. Parallel C/S pump power saving advantage over single C/S at low flow.
Click on image to enlarge
Click to get the image full size
Fig. Nº62. Best application area for parallel equally sized C/S pumps in comparison with V/S occurs when system variable head loss is low.
Click on image to enlarge
An interesting variation of parallel pumping is one V/S pump in parallel with a similarly sized C/S pump. The principal advantage of such arrangement is that only one variable speed drive (VSD) is needed to obtain a variable flow pumping arrangement. Two equally sized pumps and motors with a single VSD that can control either pump. At start-up, the VSD controls one pump and increases its speed in accordance with system need until full speed is reached. At this time, the pump is kept at full speed and VSD control is changed to the other pump, which now changes its speed in accordance with system needs. A similar reversed cycle operates as system load decreases. When properly selected and controlled, HP savings will correspond with the savings potential for a single V/S pump handling the total flow and head required but also using a lower size VSD, which means lower initial control cost.
A similar, but less costly control scheme establishes one pump as C/S only, the second as V/S only. In this case, at start-up, the V/S increases pump speed in accordance with system needs until a set control point is reached, at which time the C/S pump is started.
The V/S continues in operation, meeting increasing system flow needs as required. As before, a similar but reversed cycle occurs as load decreases.

Variable Speed Pumps
Variable speed pumping by the use of VSDs, has grown common in recent years as people have become more familiar with the technology and as costs for VSDs have gone down. With a VSD, pump head as well as flow are both reduced to handle part load situations. In the right kind of application, this can result in large savings in operating costs.
The V/S pump must operate at the intersection of its "speed" curves with the system curve. Thus, at 50 % speed, the V/S pump will provide 50 % design flow and 25 % design head and reduced power draw of 12.5 % of design point HP, due to a square relationship between flow-head, and a cubic one between pump speed-HP draw. It should be noted, however, that variable speed pumping is not a cost saving panacea. A meaningful energy savings payback with V/S systems is only possible if the designer has followed time tested design fundamentals in the application of a V/S pumping system.
Some designers attach overriding importance to pumping costs, to the extent that the design of the plant appears to be primarily determined by this consideration, without tacking into account the effects these choices have on comfort. It is true that pumping costs may be fairly accurately estimated, which is a powerful incentive to take them into account. In a balanced constant flow distribution system, the real pumping costs, in percentage of the production unit’s seasonal consumption, are around 6 to 12 % in cooling applications.
In order to achieve greatest pumping energy saving, a constant differential pressure control should be kept at the most remote unit terminal. On the other hand, if in a direct return distribution circuit, all terminal units work al 50 % load, except terminal closest to the pump that needs full flow, the differential pressure available will be insufficient at this point and design flow will not be attained at this terminal unit. The closest unit will then be underfed. However, coil performance is inherently non-linear so a reduction in flow is not matched by an equivalent in coil capacity. From
figure 63 it can be seen that variations from the design flow rate down to approximately 50 % of the design requirement have a relatively negligible effect on the overall heat transfer or system performance, assuming supply water temperature is at design condition. These capacity shortages are most likely within the error (or safety factor) of the engineer’s design load calculations and are unlikely to affect the space comfort levels.


In case of such flow variation would affect the space comfort level, relocation of the controlling pressure differential taps from the end to the center of the circuit, will provide higher differential pressure available and thus flow closer to design in the terminal nearest to the pump. In other words, it means to reduce energy saving in order to ensure the required comfort level.
Several approaches about where to establish the differential pressure control in the circuit could emerge based on the type of the building, comfort standards required, and other subjects. It seems, we are again facing an engineering trade-off between comfort and energy saving that must be carefully evaluated at each particular project.

Click to get the image full size
Fig. Nº63. Typical cooling coil characteristic.
Click on image to enlarge

 

Home | | Link To Us | | Privacy Policy | Contact Us

< Copyright www. nanomagnetics.org 2007>