Constant flow systems
have limited applications for multiple chillers piped
in parallel and serving multiple cooling loads. When
the system operates near full load, performance is
satisfactory as all chillers and pumps are operating.
However, constant flow systems have problems during
part-load or off-peak conditions. Consider
a constant-flow primary-only chilled water system
(Figure 70) with three
chillers fed by two pumps and a part load condition
small enough so that two chillers can handle the load.
Fig
Nº70. Constant-flow
primary-only chilled water system.
Click on image
to enlarge
By turning off one chiller and allowing
the flow to continue through the down machine, the supply
temperature from the plant increases due to the mixing of
water from the chiller that has been off, with the water
of the chillers that remain “on-line”. This
creates a step reset of the supply water temperature and
at the same time, pumping energy is wasted unnecessarily
in the evaporator of the chiller that was stopped.
The only way to counter the supply
temperature degradation is to drop the temperature
of the water leaving the active chillers, but this
complicates the operation and/or controls, making
it an unsatisfactory option. This scenario shows
the severe limitations of the constant-flow primary-only
scheme to face real life thermal load fluctuations
in an efficiently manner.
On the other hand, a primary/secondary
constant flow scheme with each chiller having a dedicated
primary pump (Figure 71),
allows shutting down a chiller and its pump without
affecting the secondary flow. It is possible because
both circuits are hydraulically independent. This
way the system face the variable thermal load without
having to keep on-line all chillers and pumping energy
saving are realized during periods of low loads.
Now consider a similar system with three identical
chillers operating in parallel designed to cool
55 F (12.8 C) chilled water return to 45 F (7.2
C) chilled water supply. A 50 % drop in load
could be faced with two chillers, provided that
some supply temperature degradation is allowed.
Fig. Nº71.
Constant flow primary/secondary
chilled water system
Click on
image to enlarge
It means facing
a 50 % cooling load with around 67 % of the total
production flow of the plant. It is of course a more
efficient strategy than keeping in service all production
units and theirs pumps at all loads.
However, chiller sequencing in a constant flow system
does not change really the primary loop into a true
variable distribution because the flow remains a higher
percent than load. Additionally, although some primary
flow variation is allowed, it can be done only in
a stepped way with as many steps as chillers in the
plant.
Shutting down a chiller in a primary/secondary constant
flow system with multiple chiller piped in parallel
means to break the design condition balance between
production flow (primary loop) and distribution flow
(secondary loop). As secondary circuit flow remains
constant, the excess flow will run through the common
pipe in the direction towards the secondary pumps
creating a mixing point and further degradation of
the supply temperature.
This reduces the cooling capacity of
the coils, especially latent cooling capacity which could
mean a loss of humidity control in the zones. Additionally,
the negative effect of capacity reduction due to higher supply
temperature, demands sometimes the selection of the next higher
available size for the coils.
The current standard design for central chilled
water plants with multiple chillers and multiple
cooling loads is the constant-flow primary/variable-flow
secondary scheme (Figure 72).
The primary pumps are typically constant volume,
low head pumps intended to provide a constant flow
through the evaporator of the chiller. The most
common arrangement in the primary loop is chiller-pump
in tandem, so primary pumps are sequenced with chillers.
Chiller capacity is staged in response to rising
leaving chilled-water temperature
(T1 in figure 72). A chiller is staged off
when flow in the bypass exceeds the design flow
of one chiller.
Fig. Nº72.
Constant-flow
primary/variable-flow secondary chilled water
system.
Click on image
to enlarge
This can be determine by monitoring
the bypass temperature (T2), the return temperature (T3),
and mixed return temperature (T4). Since the chilled-water-flow
rate in the primary loop is known to be a good approximation,
the flow rate through the bypass can be calculated using
these temperatures. Alternatively, a flow meter in the
bypass line can be used to measure the excess primary
flow directly.
The secondary pumps deliver the chilled water from the
common pipe to coils then back to the common pipe. These
pumps are variable-speed pumps controlled from differential
pressure sensors located remotely in the system or from
cooling coil valve position, thus secondary flow tracks
the continuously variable thermal load. Pumping energy
saved this way provides significant energy savings relative
to constant-flow schemes (primary-only and primary/secondary).
However, primary flow variation remains stepped which
avoids achieving the ideal correspondence between load
and flow.
Low delta-T syndrome in chilled water
plants When the secondary circuit return
water temperature is lower than design temperature, chillers
can not be loaded at their maximum capacity. If the chillers
in a chilled water plant designed to cool 55 F (12.8 C)
chilled water return to 45 F (7.2 C) are receiving their
design flow rate at 52 F (11.1 C) rather than the design
temperature of 55 F, the chillers will be loaded at the
ratio of: Where: CHL (%):
Percent chiller loading CWRTR:
Real chilled water return emperature CWSTD:
Design chilled water supply temperature CWRTD:
Design chilled water return temperature
In this case:
The delta-T (the difference
between return and supply chilled water temperature) in
the plant has been lowered from 10 F design condition to
7 F, then chillers will be unloaded a 30 %.
In variable flow systems, it is assumed that delta-T will
remain relatively constant at all loads. Then the flow must
vary proportionally with the load. Most variable-flow systems
are designed based on this assumption and fail to perform
well if the delta-T does not stay relatively constant. The
fact is in almost every real-world chilled water plant,
delta-T falls well below design levels, particularly at
low loads. The low delta-T “syndrome”, as it is known, causes
the plant operators to run extra pumps and chillers to meet
the load, which in addition to reducing the plant’s cooling
output capacity, wastes energy. The system may be keeping
the building cool but it is inefficient and a lot of chiller
capacity is being wasted. Table 1 shows some causes and
mitigation measures for low delta-T syndrome.
Table
1 Some causes and measures against low delta-T syndrome:
Cause
Measure
Improper setpoint or controls calibration:A modest drop in supply air temperature of an
AHU can cause coil flow rate to be doubled and delta-T
to drop in half.
Controls
must be calibrated and setpoints must be checked
regularly. Use of pressure independent delta-P control
valves or automatic flow control valves.
Using three-way valves: Three-way valves by their nature
bypass supply chilled water into the return line,
causing chilled water return temperatures lower
than design. This exacerbates low delta -T problem.
Do
not use three-way valves in variable flow system.
Two-position bypass valves across supply and return
lines, strategically situated and controlled properly
is preferred to ensure minimum flow.
Poor two-way valves selection: An improperly sized two-way control
valve may consume more water flow when open than
the design calls for. With full flow through the
coil, at partial loads the delta-T will invariably
be lower than design.
Select
the control valves considering the pressure drop
of the load served and the available differential
across the supply and return mains. Manufacturers
usually recommend that wide-open control valve pressure
drop be equal to or grater than the pressure drop
of the coil plus the pipe and fittings connecting
them to supply and return mains.
Reduced coil effectiveness: Coil transfer effectiveness is reduced
by water side fouling, air side fouling, air side
deterioration, non uniform air distribution across
the cooling coil, and coil bypass air. Any reduction
in coil effectiveness increases the flow rate of
water required to deliver the desired leaving water
temperature, thus reducing delta-T.
Control
water side fouling by proper chemical treatment.
Reduce air side fouling by cleaning coil faces and
filters periodically.
Variable primary-flow scheme, potential benefits
Among the variable flow schemes, variable-primary
flow (VPF) chilled water systems are of much current interest.
A VPF system consists of single or multiple chillers with
a unique set of pumps that moves the water through the
chillers and distribution system to the cooling load.
The cooling output at each coil is controlled with two-way
valves. A bypass line with a two-way control valve diverts
chilled water from the supply into the return line to
maintain either a constant or minimum flow through the
chiller(s).
The VPF approach has three main potential
advantages over the primary/secondary system: energy and
operating costs savings, first cost savings, and better
ability to deal with low delta-T syndrome. Energy savings
are possible because no excess flow recirculates from
supply to return through decoupling lines or three-way
valves. In theory, every bit of supply water, without
any mixing, must pass through a load before returning
to the plant. Energy savings are also possible when conditions
permit flow to one or more chillers to exceed design flow.
If outside wet bulb temperature is below the design value,
as it is over 95 percent of the year, the condensing temperature
will be also lower, giving each chiller additional capacity.
If more water can be put through the chiller, this extra
capacity can be tapped.
The first cost of a VPF system is likely to
be lower than that of a primary/secondary system simply
because two set of pumps are replaced with one.
As regards dealing with low delta-T syndrome,
VPF controls permit flow through evaporators to be increased
above design value, making it possible to adjust to less
than ideal chilled water return temperature.
However, VPF approach is not a panacea. Chiller
sequencing requires more care in order to achieve stable
operation during simultaneous flow and load changes. Additionally,
the low chiller flow bypass control adds further complexity.
In short, the VPF system is both less expensive and more
efficient than a primary/secondary system, provided that
control issues associated with variable primary flow are
handled properly.