hola

En Español
 
 
  Systems
     
Variable Volumen
 
  Hydraulics
 
  Energy Efficiency
 
  Equipment
 
   

Page Views
6131
Back to www.nanomagnetics.org
 
    Contact US
    Advertise with Us
    Related Links

Primary-Secondary Schemes
Constant volume/Constant speed

Primary-secondary pumping is a tool HVAC engineers have been using for nearly 50 years to accomplish the objective of designing the most cost-effective pumping system while meeting the client’s needs. The ASHRAE/IES Standard 90.1-1989 User’s Manual “highly recommends” primary-secondary pumping for “systems with large, high pressure drop distribution systems such as those serving campuses and airports”. Primary circuit is the place where chilled water is produced and its principal component is the chiller. The secondary circuit is responsible for the distribuition of the chilled water to the terminal units. Among the components of the secondary circuits are pumps, terminal units such as fan-coils and air handling units (AHU) and control valves.

Click to get the image full size
Fig Nº1. Common pipe design principles.
Click on image to enlarge
Primary-secondary pumping is simple in theory as well as operation. It is based on a simple fact: when two circuits are interconnected, flow in one will not cause flow in the other if the pressure drop in the piping common to both is eliminated. To ensure a low pressure drop (less than 1.5 ft) on the common pipe the length of this pipe should be kept very short, and the supply and return tees to the secondary circuit should be a maximum of three pipe diameters apart. By keeping the pressure drop very low, water that is flowing in the primary loop will not flow into the secondary circuit until its circulator turns on. That way the hydraulic isolation between both primary and secondary circuit is achieved (Fig Nº1) .

IIn the primary circuit the chilled water produced circulates thanks to pumps installed generally in tandem with each chiller. A separate circulator is installed in the secondary circuit to establish flow. This circulator is sized to move the flow rate and to overcome the pressure drop of its circuit only. The circulator should be located so it is pumping away from the common pipe and discharging into the secondary circuit. This causes an increase in pressure in the secondary circuit rather than a reduction in pressure which would occur if the pump were located on the return pumping towards the common pipe.
The Primary-secondary pumping provides the means for the constant volume pumping of the low horsepower primary pumps through the chiller. These pumps are lower horsepower than the secondary pumps because they only have to overcome the friction loss associated with the chiller, pipes, and valves in the primary loop. The chiller pumps are balanced to the design flow rate. Pump impellers should be trimmed to minimize the pressure drop across the valve on the discharge of the pump. This is an important energy saving measure. The secondary pumps, in contrast, are higher horsepower because they must overcome the friction loss associated with the secondary loop: the distribution piping, fittings, valves, coils, etc.
The volume of water circulating in the secondary circuit is constant at all times because of the three way control valve on each terminal unit of the system. When no chilled water is needed in the terminal unit the three way control valve opens its by-pass way returning chilled water without entering the coil of the terminal unit. Even in the extreme case of chilled water inlet way of all terminal units were closed, the volume of chilled water flowing in the secondary circuit would remain constant due to the opening of an alternative path (by-pass way) on each control valve. When there is no mean, as an inverter, that allow the variation of the pump speed rotation, it would operate at its rated speed at all times. That is why such systems are called constant volume/constant speed (Fig. Nº2).

Most chilled water systems are design so that secondary supply temperature equals primary supply temperature. This requirement leads to a simple design rule: primary circuit flow should equal or slightly exceed secondary circuit design flow rate .When the primary flow equals secondary flow there is no chilled water flowing through the common pipe and the supply and
Click to get the image full size
Fig. Nº2. Constant volume/constant speed primary-secondary pumping system.
Click on image to enlarge
return temperatures of both circuits are also equal (Fig.Nº3).
However such situation corresponds only to the full load condition. At part load when one or two chillers go off, the primary flow falls below the secondary flow.Whenever the flow is greater in the distribution loop than in the production loop, the excess flow in the common pipe is in the direction towards the secondary pumps. The result will always be a blending of the return water with the supply water at a temperature higher than what the chiller produces (Fig. Nº4). The outcome is terminals receiving supply water at a higher temperature and it could mean a loss of humidity control in the zones. A higher supply water temperature must be considered during the coil selection process.
Click to get the image full size
Fig. Nº3. Secondary flow equals primary flow.
Click on image to enlarge
Click to get the image full size
Fig. Nº4. Secondary flow grater than primary flow.
Click on image to enlarge
Other options can be considered. For example, chiller temperature reset can be employed. Within the limits of the type of machine, chiller temperatures can be reset to a lower temperature to compensate for the increased load and secondary flows. In essence, more capacity is provided at a lower operating efficiency. The increase in cost of chiller operation due to the lowering of the chiller supply temperature can range from 1 to 3 percent per degree of reset. This is a very desirable alternative, especially when large chillers are in use. The longer the start of a lag chiller can be delayed, the better it will perform when it is finally brought on line.
If a small portion of the load requires a fixed temperature, a small chiller in series with the load may also be considered.Many chilled water systems, however, and most hot water, can be design so that secondary circuit design supply water temperature is different from the primary water supply temperature. The Fig. Nº5 illustrates one of the outstanding advantages of primary-secondary pumping; that the primary circuit can be designed for very high temperature drops so that the primary flow and consequently pumping horsepower and pipe cost can be reduced. It should be emphasized that the primary circuit serves only a heat conveyance function and that its temperature drop or rise can be entirely different from the secondary circuit it serves.
Click to get the image full size
Fig. Nº5. Primary-secondary system with the primary circuit designed with a high temperature drop.
Click on image to enlarge

In general, the system design where secondary circuit flow rate is grater than primary provides smooth reset controllability, allows deep primary circuit temperature drops and can be used to grate advantage in the numerous primary-secondary control arrangements made possible. Actually, the most of the primary-secondary designs establish that the primary circuit flow will be equal to or less than secondary flow. It means that in such systems the return temperature of the primary circuit will always be equal to secondary return.

 

Home | | Link To Us | | Privacy Policy | Contact Us

< Copyright www. nanomagnetics.org 2007>