hola

En Español
 
 
  Systems
 
  Hydraulics
     
Piping Layout
Circuit Balance
 
  Energy Efficiency
 
  Equipment
 
   

Page Views
4370
Back to www.nanomagnetics.org
 
    Contact US
    Advertise with Us
    Related Links

Basics of Hydronics Systems
In chilled water systems, water as a secondary refrigerant, is distributed throughout the entire hydraulic network in order to achieve the design heat transfer in every coil of the building. A heat load is the rate of heat transfer from the case coils required to maintain an environment comfort standard. The liquid flow rate required to transport a given heat load is determined as follows:

Flow rate required:

Where:

LFR: Liquid flow rate (gal/min)
HL: Heat load (BTU/hr)
D: Liquid density (water density = 8.34 lb/gal)
SG: Liquid specific gravity (water specific gravity = 1)
SH: Liquid specific heat (water specific heat = 1 BTU/lb-°F)
DeltaT: Liquid temperature change during heat transfer process (°F)

The required pump head can be calculated by applying Bernoulli’s equation. Bernoulli’s relationship applies to any pumping system but the typical hydronic system, as chilled water loop, is a special case. As water re-circulates, picking up heat at one heat exchanger (AHU or fan-coil) and dropping it off at the other (chiller’s evaporator), points a and b could be defined at the same point. In closed systems the first three terms of the Bernoulli equation equals zero. Solely the friction of the system determines pump head.

Bernoulli’s relationship:

Where:
H: Pump head required to move water from the point a to point b in the system (ft)
P: Pressure at points a or b (lb/ft2)
Ganma : Liquid density (water density = 62.4 lb/ ft3)
Z: Elevation of the liquid surface at a or b from any constant reference level (ft)
V: Velocity at a or b (ft/sec)
g: Gravitational constant (32.2 ft/sec2 )
hfriction: Friction loss in the pipes, heat exchangers, coils and fittings in ft-lb of work per pound of liquid required to overcome friction (ft)

The friction loss in a hydraulic system comes from the head losses in components such as evaporator heat exchanger, cooling coils and control valves. Equipment manufacturers provide these component head losses measured in feet of head loss or pounds per square inch difference (psid) at some specific flow rate. Other sources of friction loss in a hydraulic system are pipes and fittings that can represent a significant amount of friction loss in large systems. The total friction loss of all these components, calculated at the design flow rate, determines the pump head required.

The Darcy-Weisbach equation is a commonly used empirical expression for friction head loss in piping:

Darcy-Weisbach equation:

Where:

hfriction: Friction head loss (ft)
f: Friction factor
L: Length of the pipe (ft)
D: Diameter of the pipe (ft)
V: Average flow velocity (ft/sec)
g: Gravitational constant (ft/sec2)

Some important conclusions arise from the Darcy-Weisbach relationship:

• Long, slim pipes have greater friction loss than short, wide pipes, all else being equal.
• Friction head loss is a squared function of fluid velocity so its small change will cause a greater one in friction head loss.
A wider analysis of the Darcy Weisbach equation leads to state that system head loss is a squared function of system flow:

Head-flow relationship:

In theory, friction losses which occur as liquid flows through a piping system must be calculated by means of complicated formulae, taking into account such factors as liquid density and viscosity, and pipe inside diameter and material. Luckily, these formulae have been reduced to tables and charts which, though somewhat tedious and repetitive, are nevertheless not too complex. Table 1 shows a typical pipe friction table for water at 60° F flowing through schedule 40 steel pipes. If the pipe schedule or material is other than schedule 40 steel pipes, a different table or an adjustment to the table must be used. Friction data for other pipe materials and inside diameters are often found in engineering data tables, or are sometimes available from the manufacturers of pipe.
Table 1 Pipe Friction: Water/Schedule 40 Steel Pipe (fragment)

U.S.

Gallons per minute

2 In. (2.067" I. D.) 2 1/2 In. (2.469" I. D.) 3 In. (3.068" I. D.) 3 1/2 In. (3.548" I. D.)

U.S.

Gallons per minute

V V2/2g hf V V2/2g hf V V2/2g hf V V2/2g hf
30 2.87 0.128 1.82 2.01 0.063 0.75             30
35 3.35 0.174 2.42 2.35 0.085 1.00             35
40 3.82 0.227 3.10 2.68 0.112 1.28             40
50 4.78 0.355 4.67 3.35 0.174 1.94 2.17 0.073 0.66       50
60 5.74 0.511 6.59 4.02 0.251 2.72 2.60 0.105 0.92 1.95 0.059 0.45 60
80 7.65 0.909 11.4 5.36 0.447 4.66 3.47 0.187 1.57 2.60 0.105 0.77 80
100 9.56 1.42 17.4 6.70 0.698 7.11 4.34 0.293 2.39 3.25 0.164 1.17 100
120 11.5 2.05 24.7 8.04 1.00 10.0 5.21 0.421 3.37 3.89 0.236 1.64 120
140 13.4 2.78 33.2 9.38 1.37 13.5 6.08 0.574 4.51 4.54 0.321 2.18 140
160 15.3 3.64 43.0 10.7 1.79 17.4 6.94 0.749 5.81 5.19 0.419 2.80 160
180 17.2 4.60 54.1 12.1 2.26 21.9 7.81 0.948 7.28 5.84 0.530 3.50 180
200 19.1 5.68 66.3 13.4 2.79 26.7 8.68 1.17 8.90 6.49 0.655 4.27 200
220 21.0 6.88 80.0 14.7 3.38 32.2 9.55 1.42 10.7 7.14 0.792 5.12 220
240 22.9 8.18 95.0 16.1 4.02 38.1 10.4 1.69 12.6 7.79 0.943 6.04 240
260 24.9 9.60 111 17.4 4.72 44.5 11.3 1.98 14.7 8.44 1.11 7.04 260
280 26.8 11.1 128 18.8 5.47 51.3 12.2 2.29 16.9 9.09 1.28 8.11 280
300 28.7 12.8 146 20.1 6.28 58.5 13.0 2.63 19.2 9.74 1.47 9.26 300
350       23.5 8.55 79.2 15.2 3.57 26.3 11.3 2.00 12.4 350
400       26.8 11.2 103 17.4 4.68 33.9 13.0 2.62 16.2 400
500       33.5 17.4 160 21.7 7.32 52.5 16.2 4.09 25.0 500
600             26.0 10.5 74.8 19.5 5.89 35.6 600
700             30.4 14.3 101 22.7 8.02 48.0 700
800             34.7 18.7 131 26.0 10.5 62.3 800
1000                   32.5 16.4 96.4 1000

Usually velocity (labeled "V" in Table 1) is used as the criteria for choosing al least a preliminary line size, with the trade-off between piping system cost, pump capital cost, and lifetime energy costs being considered. Common velocity guidelines are 4 to 6 ft/sec for suction piping and 6 to 10 ft/sec for discharge piping.

With the design capacity and the chosen preliminary pipe size, the friction tables give the head loss in feet per 100 linear feet of pipe (labeled "hf" in Table 1). The total friction head loss in a given length of pipe will then be obtained multiplying the value found in Table 1 by the actual pipe length divided by 100.

Friction head loss in a given length of pipe:

Where:
Hf: Total friction head loss in a given length of pipe (ft)
L: Actual length of pipe (ft)
hf: Head loss per 100 linear feet of pipe (ft)

The friction loss in valves and fittings is determined by the following formula:
Friction loss in valves and fittings:

Where:
Hf: Friction head loss in a given valve or fitting (ft)
K: Resistance coefficient for the particular valve or fitting
V2/2g: Value found in Table 1 entering with valve/fitting diameters and flow rate
The value of K for the particular valve or fitting is determined using one of the charts in Figures 50(a) and 50(b), which has a different K chart for each type of valve or fitting. The K values shown in such charts are generic only. If particular valves are already chosen, the valve manufacturer may have more precise coefficients.
Click to get the image full size
Fig. Nº50(a). Resistance coefficients (K) for valves and fittings.
Click on image to enlarge
Click to get the image full size
Fig. Nº50(b). Resistance coefficients (K) for valves and fittings..
Click on image to enlarge
An example:
In order to illustrate the procedure to be followed in pipe sizing a typical chilled water distribution system and calculating its pressure drop, a three-zone loop serving the coils of their air handling units (AHU) will be used. The system is shown in Figure 51

Chiller Plant Data:

Design thermal load: 120 Ton
Chilled water supply temperature: 42 °F
Chilled water return temperature: 54 °F
Equipment Room Pressure Drop: The total water flow rate required of 240 GPM determines the system components selection and the equipment room pipe and fittings size selection. The system will use Schedule 40 steel piping and Table1 indicates that 3 ½" size will carry the design flow. The pressure drops of the system components, including piping and fittings at the equipment room, are as follows:
Click to get the image full size
Fig. Nº51. Chilled water distribution system serving a three-zone loop.
Click on image to enlarge
Component Cant. Pressure drop
Chiller's evaporator 1 2.9'
3 ½" Piping (240 GPM from A to B) 32' 1.9'
Triple duty valve 1 2.3'
90°-Elbow 8 5.1'
Flanged gate valve 1 0.2'
Equipment Room Pressure Drop to A-B: 12.4'
zone 1:
Component Cant. Pressure drop
Coil 1 3'
2 ½" Piping (80 GPM from A to D) 200' 9.3'
Screwed tee-branch flow 1 0.7'
90°-Elbow 6 2.3'
3" Piping (180 GPM from D to B) 12' 0.9'
Screwed tee-branch flow 1 1.4'
2 ½" Balance valve (wide open) 1 2.7'
Zone 1 Pressure Drop (Less control valve): 20.3'
Zone 2:
Component Cant. Pressure drop
Coil 1 2'
3" Piping (160 GPM from A to C) 3' 0.2'
Screwed tee-line flow 1 0.7'
2" Piping (60 GPM from C to B) 130' 8.6'
Screwed tee-line flow 1 0.5'
90°-Elbow 7 3.5'
2" Balance valve (wide open) 1 1.5'
Zone 2 Pressure Drop (Less control valve): 17'
Zone 3:
Component Cant. Pressure drop
Coil 1 5'
3" Piping (160 GPM from A to C) 3' 0.2'
Screwed tee-line flow 1 0.7'
2 ½" Piping (100 GPM from C to D) 220' 15.6'
Screwed tee-branch flow 1 1.1'
90°-Elbow 5 0.6'
3" Piping (180 GPM from D to B) 12' 0.9'
Screwed tee-line flow 1 0.9'
2 ½" Balance valve (wide open) 1 4.2'
Zone 3 Pressure Drop (Less control valve): 29.2'

Control Valves Selection:

In order to provide stable flow conditions, the control valves should be selected for initial pressure drops on the order of three times the coil pressure drop if possible. On the other hand, valves should generally not be sized for over 20' pressure drop because of velocity problems. The circuit with the highest pressure drop should have its valve selected first, with the other valves selected to help balance their pressure drop to this one.

Zone 3 has the highest pressure drop, with its coil pressure drop being 5' so a valve selection for 15' @ 100 GPM should be attempted. This requires a valve with a Cv of 39. The closest selection available could be a 2" valve with Cv = 34, having a pressure drop of 19.3' at 100 GPM. The total pressure drop of Zone 3 will then be 48.5' (29.2' + 19.3').

Zone 1 has a pressure drop, exclusive of its control valve, of 20.3', so a valve can be selected for the difference between this and 48.5' to balance it to Zone 3. This difference is 28.2', well over the allowable 20' maximum pressure drop. A valve, to provide 20' resistance at 80 GPM would require a Cv of 27. The closest selection available could be a 2" valve with Cv = 29, having a pressure drop of 17' at 80 GPM. The total pressure drop of Zone 1 will then be 37.3' (20.3' + 17').

Zone 2 requires a valve with a pressure drop of 31.5' (48.5' - 17') to balance it to Zone 3. Such value is again well above the allowable 20' maximum pressure drop. A valve, to provide 20' resistance at 60 GPM would require a Cv of 20. The closest selection available could be a 2" valve with Cv of 22, having a pressure drop of 16.6' at 60 GPM. The total pressure drop of Zone 2 will then be 33.6' (17' + 16.6'). The pressure drops, including control valve, are now as follows:

Zone Pipe, coil and fittings Control valve Total
1 20.3' 17' 37.3'
2 17' 16.6' 33.6'
3 29.2' 19.3' 48.5'

Zone Balance:
In order to balance Zone 1 to Zone 3, the balancing valve will have to be set at 3.8 turns to provide 11.2' (48.5' - 37.3') of additional resistanceat the 80 GPM flow. The balancing valve of Zone 2 must be set at 3.2 turns to provide 14.9' (48.5' – 33.6') of additional resistance at the zone rated flow of 60 GPM. The balancing valve of the Zone 3 remains wide open. The settings of each balancing valve will be as follows:
Zone Valve size

Flow(GPM)

PressureDrop needed

Setting (turns)

1 2 ½" 80 11.2' 3.8
2 2 ½" 60 14.9' 3.2
3 2 ½" 100 4.2' 4
Click to get the image full size
Fig. Nº52. Curve of the pump selected.
Click on image to enlarge

Total System Pressure Drop:

Once all three zones have been balanced at their design flows, with pressure drops corresponding to Zone3's pressure drop of 48.5', it is now possible to calculate the total system pressure drop as follows:

Total system pressure drop = Equipment room pressure drop + Zone's pressure drop
Total system pressure drop = 12.4' + 48.5'
Total system pressure drop = 60.9'

A pump may now be selected for 240 GPM @ 60.9' head. A pump with an 8" impeller and 7½ HP is selected for this application. The Figure 52 shows the pump curve.
 

Home | | Link To Us | | Privacy Policy | Contact Us

< Copyright www. nanomagnetics.org 2007>